Installation & Owners ManualPRO-C SeriesEnergy Recovery VentilatorFor Carrier® HJ, TM and TF Rooftops(Sizes 3 to 12.5 ton)High Performance Ventila
Pro-C Series8Supply/Exhaust Airflow DampersAll PRO-C units have airfl ow dampers on the outdoor air intake and exhaust air outlet that are fi eld adjust
Pro-C Series9ControlsBasic PackageThe basic PRO-C unit ships with no controls. The standard wiring package provides connections for the starting/stopp
Pro-C Series10Optional Stop/Jog Economizer And Wheel Frost Protection (SMX70 Controller)The stop/jog economizer option is used during moderate outdoor
Pro-C Series113Ø Circuit Diagram, PRO-C-1000Outdoor Air Damper Actuator:Belimo Optional Stop/Jog Controller:310-1875 Assembly (observe polarity)Motion
Pro-C Series12Outdoor Air Damper Actuator:Belimo Optional Stop/Jog Controller:310-1875 Assembly (observe polarity)Motion Detector SensorOptionalModel
Pro-C Series13/UTDOOR!IR$AMPER!CTUATOR3UPPLY&AN2EMOTE3TART3TOPBYOTHERSFACTORYJUMPERED6!5,#L8&-230/PTIONAL4HERMOST
Pro-C Series14F1L1H1cutoutairflow switch SCL2L3H3F2123Solitechmaster controllerSCSCfuseH1H2to main panelon SP unitremote duct statwith set point adjus
Pro-C Series15Segregated Exhaust Adapter DimensionsACCESSOPENINGAIREXHAUSTISOMETRIC VIEWBDAC2.32"TYPICALUNIT SIZE A B C DPRO-C-1000 10.83 10.83 2
Pro-C Series16Wheel CassetteFRONTSIDE1/2" deflectionScrewScrewMOTORThe wheel cassette can be serviced through the front panel. The cassette can b
Pro-C Series17PLAN VIEWSIDE VIEWAIRFLOWAIRFLOWAIRFLOWPANELELECTRICAL PANELPro-C UnitPREHEATERWDCHCBBALPRECONDITIONERELECTRICALModel#Dimensions (inches
Pro-C SeriesTable of Contents©2001-2007 ERV Systems®. All rights reserved.The information in this technical guide is furnished for informational use o
Pro-C Series18SUPPLYAIRRETURNAIRACCESSOPENINGEXHAUSTAIRDBAREMOVABLE PANELFOR FAN ACCESS (PRO-C-1000)ACCESS DOORFOR FAN ACCESS (PRO-C-2400)SERVICE CLEA
Pro-C Series19MaintenanceFilters – The PRO-C utilizes one-inch deep industrial grade aluminum mesh fi lters. The fi lters can be removed and washed. (Se
Pro-C Series20BeltsHow to Measure, Assemble and Install Pow-erTwist® Plus™ V-BeltsPowerTwist® PlusTM V-Belts are supplied by Fenner Drives. For addit
Pro-C Series211. Turn belt with tabs to the inside before installing.2. Determine direction of drive rotation.3. Align belt directional arrow with dr
Pro-C Series22How to Reach ERV SystemsYou can reach ERV Systems by phone, fax or e-mail.ERV SystemsPO Box 1797Columbia, MO 65205-1797Phone: (573) 886
OG 002 0807 1K GPO Box 1797Columbia, MO 65205-1797(573) 886-5400(573) 886-5401 [email protected]
Pro-C Series1Outdoor Air95°F, 110 gr/lb (C)5°F, 4 gr/lb (H)Supply Air80°F, 76 gr/lb (C)54°F, 25 gr/lb (H)Return Air75°F, 65 gr/lb (C)70°F, 32 gr/lb (H
Pro-C Series2Model DescriptionOn the front of the PRO-C is an identifi cation label (Figure 2). The specifications on the label correspond to the act
Pro-C Series3Receiving & InspectionUpon delivery, confi rm that the quantity and model(s) received matches the Bill of Lading. If there is any d
Pro-C Series4InstallationInstallation of the PRO-C unit is a relatively simple procedure, but should be undertaken in a methodical fashion, following
Pro-C Series55. Install the PRO-C support angle to the base of the carrier unit. (9 screws)6. Install the return air scoop to the return air openin
Pro-C Series6PRO-C-2400 Installation Instructions:4. Remove the end panel of the Carrier unit.3. Remove the screws from the roof of the Carrier u
Pro-C Series712. Secure the right side angle trim to the PRO-C unit with the screws provided.10. Bring the units together and set into place.14. If i
Kommentare zu diesen Handbüchern